XPLORER Ручной пульт сигнала тревоги - 59000-910


Ручной пульт сигнала тревоги - 59000-910

Operating Principles

The XPlorer Manual Call Point is designed for surface mounting and incorporates the call point assembly and a back box. The address of each call point is set at the commissioning stage by means of a six-segment DIL switch, giving a range of addresses from 64 to 126. A single alarm LED is provided on the call point. This LED is controlled, 7 independently of the call point, by the CIE. Call points can be remotely tested from the control and indicating equipment by transmission of a single bit in the communications protocol. Call points respond by providing a value of 64 which corresponds to the alarm value. The CIE will recognise this response as a test signal and will not raise a general alarm.

ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ

Address Range: 64 to 126
Call Point Type: Break Glass
Weight:

190g

Call Point Principle: Operation of a switch
Alarm Indicator: Red Light Emitting Diode (LED)
Type Code: (2 1 0 4 3)
1 1 1 1 1
Supply Wiring: Two-wire supply, polarity sensitive
Loop connections: Flying leads with spade terminals
Supply Voltage: 17 to 28 Volts dc
Quiescent Current: 270μA
Power-up Surge Current: 650μA
Maximum Power-up Time: 4 seconds
Alarm LED Current: 1mA
Normal Analogue Value: 16
Alarm Level Analogue Value: 64
Max. continuous operating: +60°C
Min. continuous operating: 0°C
Min. operating: -20°C
Storage: -30°C to +80°C
Humidity: 0 to 95% relative humidity (no condensation)
Vibration, Impact and
Shock:
To prEN54–11
IP Rating: 53
Dimensions: 87mm x 87mm x 52mm
Materials: Housing: Red
polycarbonate/ABS