XPLORER Приемно-контрольный прибор, 59000-810
| Приемно-контрольный прибор, 59000-810 |
Operating Principles
The XPlorer Output Unit provides a voltage-free, single pole, change-over relay output. The change-over contact is operated by an output bit. The Output Unit returns an analogue value of 16 under all conditions.
Protocol Bit Usage
The control equipment transmits a 10-bit message to the Output Unit:
The output (or forward command) bits from the control panel have the following function:
- Output bits 2 and 1 are not used.
- Output bit 0 controls the relay.
The seven bits which are then transmitted by the control panel correspond to the address (as set on the lower 6 bits of the DIL switch with an internal preset high bit) of the device to be polled. The 6 bits of the DIL switch give an addressable range of 64 to 126.
A response message is then sent by the Output Unit to the control equipment:
The interrupt bit is always set to logic ‘0’
The analogue value bits are sent to return a preset value of 16 under all conditions.
The input bits are not used by the Output Unit.
The type bits are used to identify the type of unit responding. The type code of the Output Unit is 01000 (bits 2,1,0,4,3 respectively).
The Output Unit sends seven bits of data to confirm its address.
The alarm flag is not placed by the Output Unit.
Mechanical Construction
The Output Unit is normally supplied with screws for surface mounting. It is designed for indoor use only.
ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ
Address Range: | 64 to 126 |
Operating Voltage: | 17–28V dc |
Maximum current consumption at 24V:switch-on surge, max 100ms quiescent relay operated | 3mA |
Relay output contact rating at 30V ac or dc, max: | 1A (inductive or resistive) |
Relay output wetting at 10mV dc: | 10μA |
Operating temperature: | –20°C to +70°C |
Humidity(no condensation): | 0–95% RH |
Dimensions: | 65mm x 45mm x 22mm |
Weight: | 17 to 28 Volts dc |
Quiescent Current: | 31g |