A1493 Explosive Actuator Outstation
Explosive Actuator Outstation |
Introduction
The Control Equipment A1493 Explosive Actuator Outstation provides loop control of 2 independent explosive actuator circuits and can monitor up to 3 voltage free inputs or 2 fire detection zones when used in conjunction with the A1447 Zone Monitor Unit..
The actuator outputs are controlled independently by command output bits 0 and 1.
Output circuit 2 has a built-in delay of 0.5 seconds to minimise the load on the power supply during simultaneous output operation. Each output circuit is powered by a local 24V power supply which is monitored for failure and is optically isolated from the loop.
Both outputs are monitored for open circuit faults and can be completely isolated by the removal of a fuse from each leg of the outputs.
The outstation also has a changeover relay which is operated by command bit 2.
Technical Specification
Supply Voltage: 17-25V loop derived
Quiescent Current: 1.0mA loop derived
Maximum Current: 2.5mA loop derived
Input Terminals:
- Loop connections
- 3 inputs for voltage free contacts
- External power supply
Analogue Values:
- 64 - Input 1 operated
- 48 - Input 2 operated
- 4 - Fault Input operated or local fault
- 16 - Quiescent condition
Quiescent condition: 22-28V DC
- Quiescent condition: 12mA
- Full actuator load: 6A
Outputs:
- Output rating: 3A per circuit at 24V DC
- Monitoring current: 5mA per output
- Auxiliary relay rating: 1A @ 30V DC,
0.5A @ 125V AC
Part Numbers
2500/241 A1493 Explosive Actuator Outstation
2500/240 A1447 Zone Monitor Unit