XPLORER Ручной пульт сигнала тревоги - 59000-910
| Ручной пульт сигнала тревоги - 59000-910 |
Operating Principles
The XPlorer Manual Call Point is designed for surface mounting and incorporates the call point assembly and a back box. The address of each call point is set at the commissioning stage by means of a six-segment DIL switch, giving a range of addresses from 64 to 126. A single alarm LED is provided on the call point. This LED is controlled, 7 independently of the call point, by the CIE. Call points can be remotely tested from the control and indicating equipment by transmission of a single bit in the communications protocol. Call points respond by providing a value of 64 which corresponds to the alarm value. The CIE will recognise this response as a test signal and will not raise a general alarm.
ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ
Address Range: | 64 to 126 |
Call Point Type: | Break Glass |
Weight: | 190g |
Call Point Principle: | Operation of a switch |
Alarm Indicator: | Red Light Emitting Diode (LED) |
Type Code: | (2 1 0 4 3) 1 1 1 1 1 |
Supply Wiring: | Two-wire supply, polarity sensitive |
Loop connections: | Flying leads with spade terminals |
Supply Voltage: | 17 to 28 Volts dc |
Quiescent Current: | 270μA |
Power-up Surge Current: | 650μA |
Maximum Power-up Time: | 4 seconds |
Alarm LED Current: | 1mA |
Normal Analogue Value: | 16 |
Alarm Level Analogue Value: | 64 |
Max. continuous operating: | +60°C |
Min. continuous operating: | 0°C |
Min. operating: | -20°C |
Storage: | -30°C to +80°C |
Humidity: | 0 to 95% relative humidity (no condensation) |
Vibration, Impact and Shock: | To prEN54–11 |
IP Rating: | 53 |
Dimensions: | 87mm x 87mm x 52mm |
Materials: | Housing: Red polycarbonate/ABS |